1ph or 3ph Voltage Monitoring relay
Installation: 8 Pin Socket
Model: DSP-DVR, DVR-M
Operation based on the direct line voltage detection
-
Protection: Over/Under voltage, Phase Loss, Reverse Phase, Current Unbalance
-
Indication : Voltage [Line/Average], Frequency
-
Time-Voltage operational characteristic → Define / Inverse
​
Rated Line Voltage → 100 ~ 500VAC
Over/Under Voltage protection within (+), (-) 20% to line voltage
Possible to preset operation time for over/under voltage each, respectively.

Perfect check for initial line state
a)"dt" (trip delay time) mode is preset "OFF"
-
Preset "a" in "out" mode:
Main trip output(95-98) is energized (Open → Close) in case the rated line voltage with normal forward phase state is sensed initially -
Main trip output(95-98) is trip as showing a trip cause if the initial line state is under over/under voltage, reverse phase, voltage unbalance
-
v.OFF is shown in case the line voltage is not sensed initially or voltage is dropped to zero(0) while the normal operation is doing
- Preset "b" in "out" mode:
Main trip output(95-98) is not energized (Open→ Open) in case the rated line voltage with normal forward phase state is sensed initially
b)"dt" (trip delay time) mode is preset a value(time)
-
Preset “a” in “out" mode: Main trip output(95-98) is energized (Open→ Close) after "dt" is elapsed in case the rated line voltage with normal forward phase state is sensed initially
-
Main trip output(95-98) is still opened(not trip) even after "at" is elapsed if the initial state is under phase loss, also "PL' is shown
- "rp" is shown as main trip output(97-98) is still opened(not trip) after operational trip time(0.5sec) without concerning with "dt" if reverse state is sensed initially
Trip cause is shown by characters and/or numbers
-
4 Digit Window/DVR Type
-
5 Digit Window/DVR-M Type
3 phase line voltage/ average voltage and / or frequency is shown ordery every 3sec
Alarm history, latest 8 trip events
Reset after a trip: auto or manual
Self-diagnostics to check if this relay is ready to work or not
​
​
​
​